Operating condition :
1. Apply to heating system
2. Max. system pressure: 3bar
3. Operation condition:
Ambient Temperature: 0°C~40°C
Ambient Humidity: 95%
Liquid Temprature: 20°C~85°C
Ambient temperature must be lower than liquid temperature, in order to avoid condensate water produced in the interior of stator.
4. Liquid: Clean, non-coorosive and non-explosive liquids, without any particle, fiber or mineral oil. Water/Glycol mixtures max. mixing ratio 1:1
5. Dry running no more than 10s
Setting |
pump curve |
Function |
PP1 |
Lowest proportional- pressure curve |
The duty point of the pump will move up or down on the lowest proportional-pressure curve, depending on heating demand.The head(pressure is reduced at falling heating demand and increased at rising heating demand) |
PP2 |
Highest proportional- Pressure curve |
The duty point of the pump will move up or down on the highest proportional-pressure curve, depending on heating demand.The head(pressure is reduced at falling heating demand and increased at rising heating demand) |
CP1 |
Lowest constant- Pressure curve |
The duty point of the pump will move out or in constant-pressure curve, depending on the heating demand.The head (pressure)is kept constant, irrespective of the heating demand. |
CP2 |
Highest constant- Pressure curve |
The duty point of the pump will move out or in constant-pressure curve, depending on the heating demand. The head (pressure) is kept constant, irrespective of the heating demand. |
ⅢI |
Speed III |
Pump runs at a constant speed and consequently on a constant curve.In speed lll, the pump is set to run on the Max. curve underall operating conditions. Quick venting of the pump can be obtained by setting the pump to speed lll for a short period. |
Ⅱ |
Speed Il |
Pump runs at a constant speed and consequently on a constant curve.In speed ll, the pump is set to run on the Medium curve under all operating conditions. |
I |
Speedl |
Pump runs at a constant speed and consequently on a constant curve. In speed l, the pump is set to run on the Min. curve under all operating conditions. |
AUTO (EX-factory Setting) |
|
Under"AUTO"mode, the power of pump automatically be up or down according to flow of system in certain condition. |
Night Mode |
|
Pump runs select to night mode, after one hour the power automatically down, after two hours, it will be down lowest between 5-10watt, after seven hours, the pump auto mode eliminate and recovery to original condition. |